Generator Test
If the generator is not charging or output is low go to step 6. If the battery indicator lamp does not operate correctly go to step 1.
- Turn ignition switch to the ON position. Does the battery indicator lamp come ON momentarily.
- If lamp comes ON, go to step 3. If lamp does not light at all, check bulb. If bulb is OK, check the 3-wire connector plug plus B+ terminal, in rear of the generator for proper connection or corrosion. Clean or tighten connectors as necessary.
- Start engine, the battery indicator lamp should go out after the engine starts. If lamp goes out it is OK. If not OK, go to next step.
- Check the 3-wire connector plug and B+ terminal, in rear of the generator for improper connection or corrosion. Clean or tighten connectors as necessary. If improper connection, blown fuse or short circuit repair as necessary.
- Using a voltage meter:
- Check the battery voltage before starting.
- Start engine and raise the engine speed to 1500 RPM with all electrical loads OFF.
- Check the battery voltage again, the voltage should be between 13.5 and 15 volts.
- If not OK, replace generator. If OK, go to step 6.
- Check generator output by:
- Connecting an load bank/variable carbon pile rheostat across the battery terminals. Be sure the carbon pile is in the OFF position before connecting leads.
- Connect a voltmeter across the battery terminals.
- Connect an induction ammeter clamp around the output wire of the generator.
- Start the engine, raise and hold the engine speed at 1500 RPM.
- Adjust the carbon pile so the generator output amps increase. Confirm that at least 80 amps or more can be obtained and voltage remains between 13.5 and 15.0 volts.
- The generator amperage must meet the output requirements of 80 AMPS. If amperage reading is less than specified , the generator should be replaced. These generators are not intended to be disassembled for service. It must be replaced as an assembly.